C Series 
![]()
|
Model |
20C,30C,40C,50C,60C |
|
Engine |
Cummins 4B/BT3.9 Diesel 66-102hp @ 1800rpm 55-87hp@1500rpm |
|
Generator |
12 lead brushless |
Prime Power Rating is applicable for supplying electric power in lieu of commercially purchased power. Intermittent overloads up to the standby rating are allowable. This rating may be used for continuous service in commercial applications and conforms with BS649:1958, NEMA IEEE, and DIN"a" 6270 for generator set applications.
|
Model |
80C,100C |
|
Engine |
Cummins 6BT5.9 Diesel 135-166hp @1800rpm 115-143hp@1500rpm |
|
Generator |
12 lead brushless |
Standby Power Rating
is applicable for supplying electrical power in the event of normal utility power failure for the duration of the outage. No overload capability is available for standby ratings. The rating conforms with BSA:1958, NEMA, IEEE and DIN"a" 6270 for generator set applications.|
Model |
125C, 150C, 175C |
|
Engine |
Cummins 6CT(A) 8.3 Diesel 207-277hp @1800rpm 181-241hp@1500rpm |
|
Generator |
12 lead brushless |
Specifications
|
Model (60HZ) |
20C |
30C |
40C |
50C |
60C |
80C |
100C |
125C |
150C |
175C |
|
Rated Output (KW) |
18 |
30 |
33 |
45 |
55 |
72 |
90 |
118 |
138 |
154 |
|
KVA |
23 |
38 |
41 |
56 |
69 |
90 |
113 |
148 |
173 |
193 |
|
Continuous Standby (KW) |
20 |
30 |
40 |
50 |
60 |
80 |
100 |
125 |
150 |
175 |
|
KVA |
25 |
38 |
50 |
62 |
75 |
100 |
125 |
156 |
188 |
219 |
|
Governed RPM |
1800 |
1800 |
1800 |
1800 |
1800 |
1800 |
1800 |
1800 |
1800 |
1800 |
Approximate Fuel Consumption(Gallons Per Hour)
|
Model |
60hz |
|
20C |
2.4 |
|
30C |
2.9 |
|
40C |
3.8 |
|
50C |
4.3 |
|
60C |
5.2 |
|
80C |
6.8 |
|
100C |
7.9 |
|
125C |
10 |
|
150C |
11.7 |
|
175C |
13.6 |